Network Management Card
– User Manual 34003991EN/EC Page 17/118
3 Configuration
3.1 Configure IP parameters
Once the card has started:
Connect one end of the cable (34003918) to the Service port.
If the environment sensor was previously connected, the card must be restarted in order to access the configuration
menu.
Connect the other end of the cable to the COM port (IOIOI) of a PC.
Launch a HyperTerminal™ type emulator with the following configuration:
Speed: 9600
Data bits: 8
Parity: none
Stop bits: 1
Flow control: none
"Locally reproduce the characters entered" option: deactivated.
Enter admin. The main menu is displayed:
-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
-----------------------------------------------------------------------------