Network Management Card
– User Manual 34003991EN/EC Page 27/118
4.2.1.2 "UPS status" zone: Essential information
"Active sources": (available on parallel or modular UPS)
x UPS + y UPS redundant : x indicates the minimal number of UPS necessary to power the load,
y indicates the number of UPS in redundancy.
An alarm can be generated if the number of UPS in redundancy is less than a configurable threshold. See UPS
modules section.
"Power source": indicates whether the power comes from the utility or from the UPS battery
"Output load level": indicates the power percentage used at UPS output
"Output": indicates if the different UPS outputs are protected.
"Master": indicates if the UPS main output is protected
"Group1 and Group2": indicates if the controlled outlets (if available) are powered.
The various icons showing the status of the UPS outputs are:
(green outlet)
Outlet powered
(red outlet)
Outlet not powered or not
protected
Battery Information :
"Battery load level": remaining battery charge (in percent).
The information is completed with the two following labels:
“Charging” : if the utility power is present and the battery charge is in progress
“Discharging”: if the UPS operates on battery.
“Fault”: if the battery is faulty.
"Remaining backup time": Estimation of the battery's maximum backup time remaining before UPS shutdown
"Battery status": Result of the last automatic battery test carried out by the UPS
Possible values are:
– OK: the test was completed correctly
– NOK: the battery needs to be checked
– Deactivated: the automatic battery test is not validated on the UPS