MGE UPS Systems 66102 Manuel d'utilisateur Page 72

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 118
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 71
Network Management Card
– User Manual 34003991EN/EC Page 72/118
6 Configuration via RS232
Use the cord supplied with the card.
Connect the card to a computer equipped with a hyperterminal type emulator. The serial link must be set at 9600
baud, 8 bits, no parity, 1 stop bit, and without flow control.
Check that UPS power is on.
Enter the admin password (not modifiable).
The menu is in English only.
-----------------------------------------------------------------------------
EATON
NETWORK MANAGEMENT CARD
-----------------------------------------------------------------------------
1 : Reset
2 : Network configuration
3 : Set Login Password to Default
4 : Return to Default Configuration
0 : Exit
-----------------------------------------------------------------------------
Vue de la page 71
1 2 ... 67 68 69 70 71 72 73 74 75 76 77 ... 117 118

Commentaires sur ces manuels

Pas de commentaire